Shenzhen Yongda Xing Electrical Equipment Co., Ltd.
Language
ATS automatic switching supporting project
Introduction of ATS conversion cabinet is mainly composed of control elements and circuit breakers, which can be manually or automatically controlled for power transmission. The structure is simple and easy to operate, and the operator is easy to master the use method. Its function can meet the needs of all kinds of users, switch cabinet can be applied to the generator set for power on and off, can also be used for other power distribution equipment.
subcategory:
Key words:
ATS automatic switching supporting project
Product Details
|
Serial Number
|
Project
|
Preset Value
|
Numerical range
|
|
1
|
Mains low voltage fault value
|
AC187V
|
AC0~220V
|
|
2
|
Mains high voltage fault value
|
AC242V
|
AC220~286V
|
|
3
|
Mains high frequency fault value
|
52HZ
|
50-65HZ
|
|
4
|
Mains low frequency fault value
|
48HZ
|
45-50HZ
|
|
5
|
Mains fault confirmation delay time
|
10 seconds
|
0-9999 seconds
|
|
6
|
Delay time of mains power supply
|
10 seconds
|
0-9999 seconds
|
|
7
|
Starting delay time of generator set
|
15 seconds
|
0-9999 seconds
|
|
8
|
Generating low voltage fault value
|
AC187V
|
AC0~220V
|
|
9
|
Generating high voltage fault value
|
AC242V
|
AC220~286V
|
|
10
|
Generating high frequency fault value
|
52HZ
|
50-65HZ
|
|
11
|
Generating low frequency fault value
|
48HZ
|
40-50HZ
|
|
12
|
Generation fault confirmation delay time
|
10 seconds
|
0-9999 seconds
|
|
13
|
Delay time of power generation and supply
|
10 seconds
|
0-9999 seconds
|
|
14
|
Engine cooling delay time
|
300 seconds
|
0-9999 seconds
|
|
15
|
Type of transfer switch
|
Type 1
|
Type 1 Type 2 Type 3
|
|
16
|
Address
|
0 (not set)
|
0 (not set) 1-128
|
Monitoring function: including all measurement data, control function, operation control parameter setting
5. supply and install imported 1250A ATS automatic conversion cabinet materials as follows:
|
Serial Number
|
Specifications
|
Quantity
|
|
1
|
1250A Switch
|
1 set
|
|
2
|
1250A tinned copper palladium (10mm * 100mm * 2 purity 99.9)
|
Group 1
|
|
3
|
ATS digital intelligent automatic controller
|
1
|
|
4
|
1250/5 C.T
|
3
|
|
5
|
1250A Ammeter
|
3
|
|
6
|
380V voltmeter
|
1
|
|
7
|
voltage selector switch
|
1
|
|
8
|
DC24V 3A automatic charger
|
1
|
|
9
|
Screws and accessories
|
1 item
|
Hotline: 400-6088-009